Device designation |
HR 1300
|
Type |
E48/25WBrug-1GRM01 |
Rated output power |
1300 W |
Input |
single-phase |
Voltage |
110V/230V -18% /+15% |
Max. current per phase |
8 A (110V, 230V), sinusoidal |
Frequency |
45 - 65 Hz |
Power factor |
Cos φ≈1, EN 61000-3-2 |
Output |
IU-characteristic, DIN 41773 |
Rated voltage |
24 V, 48 V |
Characteristics: |
|
Rated voltage, static regulation |
± 1 % |
Rated current |
25A at 24V |
Current limiting |
At I rated, short-circuit-proof |
Psophometric noise |
< 2mV, ETS 300 132-2/ITU-T |
Efficiency |
0.86/0.91 |
Supervision |
|
Output voltage |
yes |
High temperature |
yes |
LED indicators/Display |
|
Signalling |
|
Measuring sockets for current |
yes |
General data |
|
EMC (emission) |
EN 55022/class B |
Isolation voltages |
prim.
→ PE 2000 VAC |
Protection class |
IP20, EN 60529 |
Safety |
UL 60950 / EN 60950 |
Safety class |
1, EN 60950 |
Cooling |
Forced cooling (internal fan, |
Ambient temperature |
-20°C ... +60°C with derating > 50°C |
Humidity |
max 95% without condensation |
Altitude |
Up to 2000m above sea level |
Connections |
HOT PLUG-IN |
Mains |
power module according |
Output |
ERMET with |
Signals |
|
Control |
|
Design type |
3 U, 42 TE * |
Dimensions ( H x W x D ) |
132 x 96 x 280 mm |
Weight |
2.6kg |
|
|
* 1U = 44.45mm ; 1TE = 5.08mm