Rectifier / charger - RM 18000


rm 18000

Device designation

RM 18000

 

Type

D60/250 WBrug-2GRM01

Rated output power

14400 W/18000 W

Input

Three-phase

Voltage

230/400V -20% /+15%

Max. current per phase

28 A

Frequency

45 - 65 Hz

Power factor

0.94

Output

IU-characteristic, DIN 41773

Rated voltage

24 V, 48 V, 60 V

 
Characteristics:
Direct feeding
Float charging
Boost charging
Special charging

2.06 V / cell
2.23 V / cell
2.33 V / cell
2.80 V/cell (24/48V operation)

Rated voltage, static regulation

± 1 %

Rated current

250A at 24V, 48V
250 Aat 60 V

Current limiting

at I rated, short-circuit-proof

Psophometric noise

< 2mV, ETS 300 132-2/ITU-T

Efficiency

0.94

Supervision

 

Output voltage

yes

High temperature

yes

LED indicators/Display

  • LED for Display
  • LED for operation
  • LED for fault

Signalling

  • RS 232-Interface
  • RS 485-Interface
  • Signal relay for equipment fault (SV1)
  • Signal relay for mains failure (SV2)
  • via monitoring unit



Measuring sockets for current
and voltage measrement

yes

General data

 

  EMC (emission)

EN 55022/class B

Isolation voltages

prim. → PE 2000 VAC
prim. → sec. 3000 VAC
sec.→ PE 1000 VAC

Protection class

IP20, EN 60529

Safety

EN 60950

Safety class

1, EN 60950

Cooling

Forced cooling (internal fan,
temperature controlled)

AAmbient temperature

-10°C ... +45°C without derating

Humidity

max 95% without condensation
ETS 300 019/class 3.2

Altitude

up to 2000m above sea level

Connections

Front Access

Mains

  • Terminals 6 mm²
  • PE with M8 PIN

Output

Pin M8

Signals

D-Sub 25-Pole

Control

  • D-Sub 25-Pole (Signals)
  • RS485 D-Sub 15-Pole
  • RS232 D-Sub 9-Pole

Design type

6 U, 19"    *

Dimensions ( H x W x D )

272 x 483 x 440 mm

Weight

43,5 kg

 

 

 

* 1 U= 44.45mm ; 1TE = 5.08mm

 